35 WATTS |
NO MINIMUM ORDER REQUIRED |
|
SRP-30/35 SERIES |
|
Features
- RoHS Compliant
- Universal 85-264 VAC Input
- Advanced SMT Design
- Compact 3.0" X 6.0" X 2.0" Size
- Class B Emissions Per EN 55011/22
- EMC to EN 61000-6-2 & EN 60601-1-2
- 2 Year Warranty
- UL Listed
- One to Four Outputs
- EN 60950 ITE Certification
- EN 60601-1 Medical Certification

| Source Voltage |
85-264 Voltage AC |
| Frequency Range |
47-63 Hz |
| Source Current |
|
| True RMS |
1A At 85V Input |
| Peak Inrush |
30A |
| Efficiency |
.66 -.80 (Varies by model) |
| |
ENVIRONMENTAL SPECIFICATIONS |
|
| Ambient Operating Temperature Range |
0oC to +70oC Derating:See Power Rating Chart |
| Ambient Storage Temperature Range |
-40oC to +85oC |
| Temperature Coefficient |
Outputs 1-4: 0.02%/oC |
|
| Total Output Power at 50c |
28-35 W Model Dependent |
| Output Voltage Centering |
Output 1: +/-0.25% Output 2: +/-5.0% Output 3: +/-3.0% Output 4: +/-3.0% (All outputs at 50% load) |
| Source Regulation |
Outputs 1-4: 0.5% |
| Load Regulation |
(Local Sense) |
|
| Output 1: 7.0% (0-100% Load Change) |
| (1001) 10.0% (0-100% Load Change) |
| (4001) 12.0% (0-100% Load Change) |
| (Remote Sense) 0.5% (0-100% Load Change) |
| Output 2: 5.0% (30-100% Load Change) |
| (4001,3 & 4) 10.0% (30-100% Load Change) |
| (2003, 4002) 12.0% (30-100% Load Change) |
| Output 3: 1.0% (0-100% Load Change) |
| Output 4: 1.0% (0-100% Load Change) |
| Cross Regulation |
Output 2: 5.0% Output 3: 0.5% Output 4: 0.5% (Output 1 load varied 50-100%) |
| Output Voltage Adjust Range |
Output 1: 95% to 105% |
| Output Noise |
Outputs 1-4: 1.0% |
| |
|
| Turn On Overshoot |
None |
| Transient Response |
Outputs 1-4: |
| Volt. Deviation |
5.0% |
| Recovery Time |
2 mS |
| Load Change |
50% To 100% |
| Output Overvoltage Protection |
Output 1: 110% to 150% |
| Output Overpower Protection |
Output 1&2: 110% Min. |
| Outputs cycle on/off, auto recovery |
| Output Overcurrent Protection |
Output 3&4: 110% Min. |
| Hold Up Time |
12 mS Min, 28-35 W Output 120 V Input |
| Start Up Time |
1 Second | |
|
|
|
| General |
|
Protection Class: I |
| Overvoltage Category:I |
| Pollution Degree: 2 |
| Ingress Protection IP30 |
|


|
Underwriters Laboratories File E137708/ E140259 |
UL 60950-1 First Edition UL 60601-1 First Edition
CB Report Per IEC 60950-1 (2001)First Edition All National Deviations CB Report Per IEC 60601-1 (1988) Second Edition A1,A2
|
 |
|
UL 60950-1 First Edition |
 |
UL Recognition Mark for Canada File E137708/ E40259 |
CAN/CSA-C22.2 No.60950-1-03 CAN/CSA-C22.2 No.601-1-M90 with updates 1 and 2 |
 |
TUV |
EN 60950-1:2001 EN 60601-1/A2:1995 |
 |
|
Low Voltage Directive EMC Directive | |
| Dielectric Strength |
|
| Reinforced Insulation |
5656 VDC, Primary to Secondary, 1 Sec. |
| Basic Insulation |
2121 VDC, Primary to Ground, 1 Sec. |
|
Operational Insulation |
707 VDC, Secondary to Ground, 1 Sec. |
| Leakage Current |
<300 µA Earth Leakage Current |
| Mean Time Between Failures |
100,000 Hours min., MIL-HDBK-217F, 25oC, GB |
| Weight |
1.60 Lbs. |
| |
ELECTROMAGNETIC COMPATIBILITY SPECIFICATIONS | |
| Electrostatic Discharge |
EN 61000-4-2 |
+/-8kV Contact Discharge +/-8kVAir Discharge |
| Radiated Electro-magnetic Field |
EN 61000-4-3 |
80MHz-2.5GHz, 10V/m, 80% AM |
| EFT/Bursts |
EN 61000-4-4 |
+/-2kV |
| Surges |
EN 61000-4-5 |
+/-1 kV Differential Mode +/-2 kV Common Mode |
| Conducted Immunity |
EN 61000-4-6 |
.15-80MHz., 10V, 80% AM |
| Voltage Dips and Interuptions |
EN 61000-4-11 |
30%Reduction,500ms |
| 95% Reduction,10ms |
|
60% Reduction,1s (criteria B) |
| 95% Reduction,5000ms |
| Radiated Emissions |
EN 55011/22 |
Class B |
| Conducted Emissions |
EN 55011/22 |
Class B | |
Consult factory for alternate output configuration. Consult factory for positive, negative or floating output 2. Refer to Application Information for complete output power ratings. All specifications are maximum at 25C unless otherwise stated and are subjected to change without notice. |
| Model |
Output 1 |
Output 2 |
Output 3 |
Output 4 |
Output5 |
| SRP-30A-4001 |
+3.3V/3A |
+5V/2A |
+12V/.35A |
-12V/.35A |
28W |
| SRP-30A-4002 |
+5V/3A |
+3.3V/2A |
+12V/.35A |
-12V/.35A |
30W |
| SRP-30A-4003 |
+5V/3A |
-5V/2A |
+12V/.35A |
-12V/.35A |
30W |
| SRP-30A-4004 |
+5V/3A |
-5V/2A |
+15V/.35A |
-15V/.35A |
30W |
| SRP-30A-4005 |
+5V/3A |
+24V/.75A |
+12V/.35A |
-12V/.35A |
30W |
| SRP-30A-4006 |
+5V/3A |
+24V/.75A |
+15V/.35A |
-15V/.35A |
30W |
| SRP-30A-3001 |
+5V/3A |
+12V/1.5A |
-12V/.50A |
|
30W |
| SRP-30A-3002 |
+5V/3A |
+15V/1.5A |
-15V/.50A |
|
30W |
| SRP-30A-2001 |
+5V/3A |
+24V/.75A |
|
|
30W |
| SRP-30A-2002 |
+5V/3A |
+12V/1.5A |
|
|
30W |
| SRP-30A-2003 |
+5V/3A |
-5V/3A |
|
|
30W |
| SRP-30A-2004 |
+12V/1.5A |
-12V/1.5A |
|
|
30W |
| SRP-30A-2005 |
+15V/1.5A |
-15V/1.5A |
|
|
30W |
| SRP-30A-1001 |
3.3V/9A |
|
|
|
30W |
| SRP-35A-1002 |
5V/7A |
|
|
|
35W |
| SRP-35A-1003 |
12V/2.9A |
|
|
|
35W |
| SRP-35A-1004 |
15V/2.3A |
|
|
|
35W |
| SRP-35A-1005 |
24V/1.45A |
|
|
|
35W |
| SRP-35A-1006 |
48V/.73A |
|
|
|
35W | |
| |
SRP-30/35 SERIES MECHANICAL SPECIFICATIONS |
|  |
|

|
|
|
- Each output can deliver its rated current but total output power must not exceed 28-35 watts depending on model.
- Sufficient area must be provided around convection cooled power supplies to allow natural movement of air to develop.
- A minimum load of 10% is required on output one to insure proper regulation of remaining outputs.
- Remote sense terminals may be used to compensate for cable losses up to 250mV. The use of a twisted pair is recommended as well as a decoupling capacitor (0.1 0 10µF) and a capacitor of 100µF/amp connected across the load.
- Peak to peak output ripple and noise is measured directly across a 1µF ceramic capacitor at the output terminals of the power supply cord, without the use of the probe ground lead or retractable tip, 20 MHz bandwidth.
- This product was type tested and safety certificated using the the dielectric strength test voltages listed in Table V of UL 60601-1. In consideration of clause 20.4g, care must be taken to insure the voltage applied to a reinforced insulation does not over stress basic insulation. Secondary to ground capacitors may need to be removed prior to performing a dielectric strength type test on the end product. It is highly recommended that the DC test voltages listed in DVB.1. Annex DVB are not exceeded during a production-line dielectric strength test of the assembled end product. Please consult factory for further information.
- This power supply has been safety approved and final tested using a DC dielectric strength test. Please consult factory before performing AC dielectric strength test.
| |
| |
| |
Maximum Output Power vs. Ambient Temperature(35W) | |
 |
| |
Maximum Output Power vs. Ambient Temperature(30W) | |
 |
| AC Input |
IEC 320 AC Power Receptacle |
| DC Output |
8 pin connector mates with Power Dynamics 8 pin din socket #DS-048 | |
| | | |